POQ B basic type electric actuator 60-20000NM

Type: basic type
Torque:60-20000NM
Voltage:AC220V,AC110V,AC380V,DC24,DC110,DC220 other
Control:ON-OFF
Explosion-proof:EXd II BT5  /  EXd II CT5
Top flange: ISO5211
Valve:ball valve/butterfly valve






     

    Description

    POQ Electric actuator the main technical parameters

    Shell Protection grade lP67 Nema 4 and 6    Option: lp68
    Ambient temperature -25℃ to +70℃
    Environment humidity <90% RH
    Power supply Single-phase: 24V,110V,220V,230V,240V,50/60Hz
    Three-phase: 220V,380V,415V,440V 50/6OHz DC: DC24V
    Torque switch On (NO) / off (OFF), SPDT 250V AC 10A
    (except POQ-006,POQ-010)
    Limit switch On (NO) / off(OFF),  SPDT 250VAC 10A
    Motor overheat protection Built-in thermal protection 120℃土5℃
    Stroke 90°士58 (0°~270°Optional)
    lndicator 360°Angle of view indication
    (flameproof type: continuous position indication)
    Manual operation POQ-006~POQ-060 Manual/automatic clutch mechanism
    POQ-080~POQ-2000 No clutch required
    Self-locking device Worm gear and worm mechanism provide
    Mechanical limit External adjustable bolt
    Desiccator Aluminum alloy moisture-proof resistance (anti-condensation)
    Wiring hole Standard: 2-NPT3/4”
    Optional customization: M20~M25、PG13.5、PG16、PT3/4″、PF3/4″
    Grease Molybdenum disulfide grease (EP type)
    Main material Aluminum, steel, aluminum blue steel,35CrMo, etc.
    Exterior coating Epoxy polyester powder coating
    Seismic performance Direction: x,z,y; Maximum acceleration: 12g;
    Sweep frequency: 10-55Hz;Amplitude: 0.15mm; Time 30 minutes
    lnfrared remote control No opening setting
    Explosion-proof grade Optional: EXd I BT5 EXd lI Ct5
    Potentiometer Optional: 1K-5K
    Proportional control unit lnput Output: 4-20mA
    Field control unit Optional: Process control on/off/off knob
    Bus control unit Optional
    Bluetooth communication Optional
    GPRS wireless control Optional

    Wiring diagram

    1.POQ-006B/K1~010B/K1 AC24V, AC110V,AC220V-50Hz/60Hz(BASIC  ON-OFF TYPE)

    Electric actuator wiring diagram

    2.POQ-016B/K1~800B/K1 AC24V,AC110V,AC220V-50Hz/60Hz(BASIC ON-OFF TYPE)

    Electric actuator wiring diagram

    3.POQ-006B/K1~010B/K1 AC38V,AC440V-50Hz/60Hz(BASIC ON-OFF TYPE)

    Electric actuator wiring diagram

    4.POQ-016B/K1~2000B/K1 AC380V,AC440V-50Hz/60Hz(BASIC ON-OFF TYPE)

    Electric actuator wiring diagram

    5.POQ-006B/K1~010B/K1 DC24V-50Hz/60Hz ( BASIC ON-OFF TYPE)

    Electric actuator wiring diagram

    6.POQ-016B/K1~800B/K1 DC24V-50Hz/60Hz(BASIC ON-OFF TYPE)

    Electric actuator wiring diagram

    7.POQ-006G/K2~010G/K2 AC110V,AC220V-50Hz/60Hz(COMMON MODULATING TYPE)

    Electric actuator wiring diagram

    8.POQ-016G/K2~80OG/K2 AC110V, AC220V-50Hz/6OHz(COMMON MODULATING TYPE)

    Electric actuator wiring diagram

    9.POQ-006Y/K1~80OY/K1 AC110V,AC220V-50Hz/60Hz(Non-intrusive intelligent integrated ON-OFF type)

    Electric actuator wiring diagram

    10.POQ-006Y/K2~800Y/K2 AC110V,AC220V-50Hz/60Hz(Non-intrusive intelligent integrated Modulating type)

    Electric actuator wiring diagram

    11.POQ-006Y/K1~800Y/K1 AC380V-50Hz/60Hz(Non-intrusive intelligent integrated ON-OFF type)

    Electric actuator wiring diagram

    12.POQ-006Y/K2~800Y/K2 AC380V-50Hz/60Hz(Non-intrusive intelligent integrated Modulating type)

    Electric actuator wiring diagram

    13. POQ-006S~800S AC220V-50Hz/60Hz (Super intelligent type)

    Electric actuator wiring diagram

    14.POQ-006S~o00S AC380V-50Hz/60Hz (Super intelligent type)

    Electric actuator wiring diagram

     

    Dimensions

    Basic type POQ-006B~POQ-060B/Explosion-proof basic type POQ-Ex006B~POQ-Ex060B

    POQ-006B~POQ-060B Electric actuator dimensions

    Modle A B C D E F G ΦI ΦJ 4-N ΦK 4-P ΦL 4-Q M A1
    POQ-006 280 92 77 47 171 40 50 100 50 4-M6 70 4-M8 57.15 4-M6 9/11/14/17 240
    POQ-010 280 92 77 47 171 40 50 100 50 4-M6 70 4-M8 57.15 4-M6 9/11/14/17 240
    POQ-016 316 147 90 78 208 48 63 180 70 4-M8 102 4-M10 69.85 4-M8 11/14/17/22 276
    POQ-020 316 147 90 78 208 48 63 180 70 4-M8 102 4-M10 69.85 4-M8 11/14/17/22 276
    POQ-030 341 152 98 81 218 52 63 180 102 4-M10 125 4-M12 88.9 4-M12 14/17/22 301
    POQ-050 341 152 98 81 218 52 63 180 102 4-M10 125 4-M12 88.9 4-M12 14/17/22 301
    POQ-060 341 152 98 81 218 52 63 180 102 4-M10 125 4-M12 88.9 4-M12 14/17/22

    301

    Basic type POQ-080B~POQ-230B/Explosion-proof basic type POQ-Ex080B~POQ-Ex230B

    POQ-080B~POQ-230B Electric actuator dimensions

    Modle A B C D E F G ΦI ΦJ 4-N ΦK 4-P ΦL 4-Q 4-Q M A1
    POQ-080 415 130 212 128 208 58 80 250 102 4-M10 125 4-M12 107.95 4-M12 F14

    Factory

    optional

    17/22/27 375
    POQ-100 415 130 212 128 208 58 80 250 102 4-M10 125 4-M12 107.95 4-M12 17/22/27 375
    POQ-130 415 130 212 128 208 58 80 250 102 4-M10 125 4-M12 107.95 4-M12 17/22/27 375
    POQ-170 458 145 236 146 236 66 80 280 F12(Φ125/4-M12)/Factory optional

    F14(Φ140/4-M16)/Factory optional

    F16(Φ165/4-M20)/Factory optional

    22/27/36 418
    POQ-200 458 145 236 146 236 66 80 280 22/27/36 418
    POQ-230 458 145 236 146 236 66 80 280 22/27/36 418

    Basic type POQ-350B~POQ-800B/Explosion-proof basic type POQ-Ex350B~POQ-Ex800B

    POQ-350B~POQ-800B Electric actuator dimensions

     

    Modle A B C D E F G ΦI ΦJ 4-N ΦK 4-P M
    POQ-350 620 145 236 267 110 145 80 280 160 4-M20 F14 Optional

    appearance

    36/46
    POQ-500 620 145 236 267 110 145 80 280 160 4-M20 36/46
    POQ-800 627 155 236 315 155 150 80 280 160 4-M20 254 8-M16 46/55

    Basic type POQ-1300B~POQ-2000B/Explosion-proof basic type POQ-Ex1300B~POQ-Ex2000B

    POQ-1300B~POQ-2000B Electric actuator dimensions

     






      Actuator installation

      1.lnstallation site

      1.1 Installation Precautions

      -For installation in places with explosive gas, explosion-proof actuators need to be ordered;

      – Please specify in advance if the installation is submerged ;

      – When installing the cable on site, is outer diameter must be in line with the cable that is compatible with the inner diameter of the waterproofconnector,otherwise the outdoor rainwater can enter the actuator from the waterproof cable connector and damage the internal parts;

      – Please reserve space for wiring and manual operation and maintenance ;

      1.2Ambient temperature

      – The ambient temperature is -25℃+70℃ (other temperatures can be customized);

      – When the ambient temperature is lower than -25’℃ or higher than 70℃ please contact the technical department of our company in advance to propose specific solutions;  (all series of standard dryers)

      1.3 Pipeline fluid temperature conditions

      -When used with a valve, the heat of the fuid in the pipeline will be transferred to the actuator, and the temperature of the actuator housing will rise ; if the on-site pipeline fluid is higher than 80℃, please contact our company in advance.Contact with the Ministry to propose a specific solution; (the connection with the valve needs to increase the bracket for heat insulation)

      1.4 Pipeline high frequency vibration conditions

      – Intelligent actuators under high-frequency vibration conditions require separate installation;

       

       2.Actuator output connection

      -The fange mounting hole at the bottom of the actuator is lSO5211 standard. lf the valve connection size does not conform to the standard,please contact our company’s technical department in advance to propose a specific solution;(before leaving the factory)(According to customer requirements, re-punch holes or produce brackets and connecting sleeves)

      -According to the different connecting spindles of the valve, the inner hole at the bottom of the actuator can be replaced with different sizes such as square holes , round holes and bilateral holes; the replacement method is simple, just use circlip pliers to take out the spline sleeve bottom the circlip can be replaced;

      Actuator output connection3.Installation sequence of actuator and valveInstallation sequence of actuator and valve

       Installation sequence of actuator and valve

      Note:

      This figure only shows the installation sequence and can be used as a reference. The actual actuator shall prevail.

      Note: This figure only shows the installation sequence and can be used as a reference. The actual actuator shall prevail.

      4.Electrical wiring

      -Remove the plug for external cable access, please use an explosion-proof connector or explosion-proof cable hose with an external thread of NPT3/4;

      -lf the cable connector does not meet the electrical interface of the actuator, it may cause the internal sealing level to drop and fail to meet the protection requirements, or the actuator will be damaged by water entering the inside;

      – When using electrical wires, take full waterproof measures;

      – Remove the upper cover of the actuator,use a fat-blade screwdriver to press down the metal shrapnel in the small hole on the terminal, and at the sametime the wire is smoothly inserted into the side trminal hole,pull out the screwdriver ,the internal spring clamping mechanism of the terminal can reliably clamp the wire;

      Electrical wiring

      Note:

      1.Before completing the wiring check, do not swich on the power supply. Shor-circuit and wrong wiring will cause permanent damage to the actuatord!

      2.Please pay attention to the switch instructions, please do not use brute force on the hand wheel/handle when it exceeds the fully open an fully cosed positions, so as not to cause damage to the actuator mechanism!

       






        Debugging instructions

        1.Mechanical limit adjustment

        Losen the mechanical limit screw and limit nut, turn the handwheel with the left hand and press the switch handle with the right hand in the direction of the arrow to engage the internal clutch of the mechanism to reach the manuel function state (switcing hand when the power is turned on) The handle automatically resets without human intervention), continue to rotate the handwheel clockwise to move the actuator to the fully closed position,rotate the limit screw, and stop turning when it his the internal sector worm gear.Rotate two turns to the left, and finally tighten the nut.In this way, the position of the mechanical limit when the actuator is fully closed is set. Rotate the handwheel in the fully open position counterclockwise and set it in the same way.

        Debugging instructions for electric actuator

        Note:

        POQ series 006 type to 060 type manual switch requires a switch handle (automatic reset function when power is on), 08O type to 200 type does not need a switch handle

         

        2.Electronic travel limit adjustment

        Manually close the valve to the position to loosen the switch direction limit cam, adjust it to the position where the limit switch is just pressed down, and then lock the limit cam, so that the position of the electrical limit when the actuator is fully closed is adjusted;The position when fully open can be set in the same way;

        Debugging instructions for electric actuator

         

        3.Adjustment of overload protection device

        Under the normal working pressure of the valve, adjust the overload cam so that it just touches the roller of the corresponding micro switch,but it can’t be pressed.When the required torque to openor close the valve is greater than the factory rated torque, the overload rotating shaft will rotate clockwise or counterclockwise, driving the upper overloadcam to press the micro switch to stop the function and output a set ofover torque indications.To protect the electric valve from damage.

        Debugging instructions for electric actuator

        Note:

        The overload protection device has been adjusted before leaving the factory. in principle, no further adjustment is required ,f djustment is requiredthe valve needs to be adjusted under normal working pressure conditions

         

        4.Potentiometer adjustment

        The potentiometer is used as a feedback output in the actuator, and there are three output terminals, of which the terminal pin ② is connected to the sliding arm of the potentiometer. When the terminal pin of ① is connected to the actuator to open ,the resistance between it and the sliding arm keeps decreasing one end; when the pin of terminal ③ is connected to the actuator to close the action,the resistance to the sliding arm keeps decreasing one end (note: potentiometer)There should be no resistance value crossing zero, umping phenomenon).Use the handwheel to turn the valve to the fully open position, and use a multimeter to measure it, and adjust the resistance of the terminals ①② on the wiring terminals to between 40Ω and 65Ω. If it is not correct, it can be adjusted by turning the transmission gear on the potentiometer.

        Debugging instructions for electric actuator

         

        5.Position indicator adjustment

        First close the valve to the correct position, disassemble the 3D window protective cover and 3D transparent protective cover, use an Allen key to loosen the 3D indicator column, rotate it to the correct position and lock it,and then reset and install it in turn (Picture 1). First close the valve to the correct position, disassemble the Ex upper cover, loosen the indicator plate with a Phillips screwdriver, rotate it to the positive position and lock it, and then reset and install it in sequence (Figure 2).

        Debugging instructions for electric actuator