Description
POQ Electric actuator the main technical parameters
Shell |
Protection grade lP67 Nema 4 and 6 Option: lp68 |
Ambient temperature |
-25℃ to +70℃ |
Environment humidity |
<90% RH |
Power supply |
Single-phase: 24V,110V,220V,230V,240V,50/60Hz
Three-phase: 220V,380V,415V,440V 50/6OHz DC: DC24V |
Torque switch |
On (NO) / off (OFF), SPDT 250V AC 10A
(except POQ-006,POQ-010) |
Limit switch |
On (NO) / off(OFF), SPDT 250VAC 10A |
Motor overheat protection |
Built-in thermal protection 120℃土5℃ |
Stroke |
90°士58 (0°~270°Optional) |
lndicator |
360°Angle of view indication
(flameproof type: continuous position indication) |
Manual operation |
POQ-006~POQ-060 Manual/automatic clutch mechanism
POQ-080~POQ-2000 No clutch required |
Self-locking device |
Worm gear and worm mechanism provide |
Mechanical limit |
External adjustable bolt |
Desiccator |
Aluminum alloy moisture-proof resistance (anti-condensation) |
Wiring hole |
Standard: 2-NPT3/4”
Optional customization: M20~M25、PG13.5、PG16、PT3/4″、PF3/4″ |
Grease |
Molybdenum disulfide grease (EP type) |
Main material |
Aluminum, steel, aluminum blue steel,35CrMo, etc. |
Exterior coating |
Epoxy polyester powder coating |
Seismic performance |
Direction: x,z,y; Maximum acceleration: 12g;
Sweep frequency: 10-55Hz;Amplitude: 0.15mm; Time 30 minutes |
lnfrared remote control |
No opening setting |
Explosion-proof grade |
Optional: EXd I BT5 EXd lI Ct5 |
Potentiometer |
Optional: 1K-5K |
Proportional control unit |
lnput Output: 4-20mA |
Field control unit |
Optional: Process control on/off/off knob |
Bus control unit |
Optional |
Bluetooth communication |
Optional |
GPRS wireless control |
Optional |


Wiring diagram
1.POQ-006B/K1~010B/K1 AC24V, AC110V,AC220V-50Hz/60Hz(BASIC ON-OFF TYPE)

2.POQ-016B/K1~800B/K1 AC24V,AC110V,AC220V-50Hz/60Hz(BASIC ON-OFF TYPE)

3.POQ-006B/K1~010B/K1 AC38V,AC440V-50Hz/60Hz(BASIC ON-OFF TYPE)

4.POQ-016B/K1~2000B/K1 AC380V,AC440V-50Hz/60Hz(BASIC ON-OFF TYPE)

5.POQ-006B/K1~010B/K1 DC24V-50Hz/60Hz ( BASIC ON-OFF TYPE)

6.POQ-016B/K1~800B/K1 DC24V-50Hz/60Hz(BASIC ON-OFF TYPE)

7.POQ-006G/K2~010G/K2 AC110V,AC220V-50Hz/60Hz(COMMON MODULATING TYPE)

8.POQ-016G/K2~80OG/K2 AC110V, AC220V-50Hz/6OHz(COMMON MODULATING TYPE)

9.POQ-006Y/K1~80OY/K1 AC110V,AC220V-50Hz/60Hz(Non-intrusive intelligent integrated ON-OFF type)

10.POQ-006Y/K2~800Y/K2 AC110V,AC220V-50Hz/60Hz(Non-intrusive intelligent integrated Modulating type)

11.POQ-006Y/K1~800Y/K1 AC380V-50Hz/60Hz(Non-intrusive intelligent integrated ON-OFF type)

12.POQ-006Y/K2~800Y/K2 AC380V-50Hz/60Hz(Non-intrusive intelligent integrated Modulating type)

13. POQ-006S~800S AC220V-50Hz/60Hz (Super intelligent type)

14.POQ-006S~o00S AC380V-50Hz/60Hz (Super intelligent type)

Dimensions
Super intelligent type POQ-006S~POQ-060S/Explosion-proof super intelligent type POQ-Ex006S~POQ-Ex060S

Modle |
A |
B |
C |
D |
E |
F |
G |
ΦI |
ΦJ |
4-N |
ΦK |
4-P |
ΦL |
4-Q |
M |
A1 |
B1 |
POQ-006 |
280 |
300 |
77 |
95 |
171 |
40 |
50 |
100 |
50 |
4-M6 |
70 |
4-M8 |
57.15 |
4-M6 |
9/11/14/17 |
240 |
312 |
POQ-010 |
280 |
300 |
77 |
95 |
171 |
40 |
50 |
100 |
50 |
4-M6 |
70 |
4-M8 |
57.15 |
4-M6 |
9/11/14/17 |
240 |
312 |
POQ-016 |
316 |
336 |
90 |
99 |
208 |
48 |
63 |
180 |
70 |
4-M8 |
102 |
4-M10 |
69.85 |
4-M8 |
11/14/17/22 |
276 |
348 |
POQ-020 |
316 |
336 |
90 |
99 |
208 |
48 |
63 |
180 |
70 |
4-M8 |
102 |
4-M10 |
69.85 |
4-M8 |
11/14/17/22 |
276 |
348 |
POQ-030 |
341 |
346 |
98 |
93 |
218 |
52 |
63 |
180 |
102 |
4-M10 |
125 |
4-M12 |
88.9 |
4-M12 |
14/17/22 |
301 |
358 |
POQ-050 |
341 |
346 |
98 |
93 |
218 |
52 |
63 |
180 |
102 |
4-M10 |
125 |
4-M12 |
88.9 |
4-M12 |
14/17/22 |
301 |
358 |
POQ-060 |
341 |
346 |
98 |
93 |
218 |
52 |
63 |
180 |
102 |
4-M10 |
125 |
4-M12 |
88.9 |
4-M12 |
14/17/22 |
301 |
358 |
Super intelligent type POQ-080S~POQ-230S/Explosion-proof super intelligent type POQ-Ex080S~POQ-Ex230S

Modle |
A |
B |
C |
D |
E |
F |
G |
ΦI |
ΦJ |
4-N |
ΦK |
4-P |
ΦL |
4-Q |
4-Q |
M |
A1 |
B1 |
POQ-080 |
415 |
338 |
212 |
128 |
208 |
58 |
80 |
250 |
102 |
4-M10 |
125 |
4-M12 |
107.95 |
4-M12 |
F14
Factory
optional |
17/22/27 |
375 |
350 |
POQ-100 |
415 |
338 |
212 |
128 |
208 |
58 |
80 |
250 |
102 |
4-M10 |
125 |
4-M12 |
107.95 |
4-M12 |
17/22/27 |
375 |
350 |
POQ-130 |
415 |
338 |
212 |
128 |
208 |
58 |
80 |
250 |
102 |
4-M10 |
125 |
4-M12 |
107.95 |
4-M12 |
17/22/27 |
375 |
350 |
POQ-170 |
458 |
353 |
236 |
146 |
236 |
66 |
80 |
280 |
F12(Φ125/4-M12)/Factory optional
F14(Φ140/4-M16)/Factory optional
F16(Φ165/4-M20)/Factory optional |
22/27/36 |
418 |
365 |
POQ-200 |
458 |
353 |
236 |
146 |
236 |
66 |
80 |
280 |
22/27/36 |
418 |
365 |
POQ-230 |
458 |
353 |
236 |
146 |
236 |
66 |
80 |
280 |
22/27/36 |
418 |
365 |
Super intelligent type POQ-350S~POQ-800S/Explosion-proof super intelligent type POQ-Ex350S~POQ-Ex800S

Modle |
A |
B |
C |
D |
E |
F |
G |
ΦI |
ΦJ |
4-N |
ΦK |
4-P |
M |
B1(Ex) |
POQ-350 |
620 |
353 |
236 |
267 |
110 |
145 |
80 |
280 |
160 |
4-M20 |
F14 Factory
optional |
36/46 |
365 |
POQ-500 |
620 |
353 |
236 |
267 |
110 |
145 |
80 |
280 |
160 |
4-M20 |
36/46 |
365 |
POQ-800 |
627 |
353 |
236 |
315 |
155 |
150 |
80 |
280 |
160 |
4-M20 |
254 |
8-M16 |
46/55 |
365 |

Actuator installation
1.lnstallation site
1.1 Installation Precautions
-For installation in places with explosive gas, explosion-proof actuators need to be ordered;
– Please specify in advance if the installation is submerged ;
– When installing the cable on site, is outer diameter must be in line with the cable that is compatible with the inner diameter of the waterproofconnector,otherwise the outdoor rainwater can enter the actuator from the waterproof cable connector and damage the internal parts;
– Please reserve space for wiring and manual operation and maintenance ;
1.2Ambient temperature
– The ambient temperature is -25℃+70℃ (other temperatures can be customized);
– When the ambient temperature is lower than -25’℃ or higher than 70℃ please contact the technical department of our company in advance to propose specific solutions; (all series of standard dryers)
1.3 Pipeline fluid temperature conditions
-When used with a valve, the heat of the fuid in the pipeline will be transferred to the actuator, and the temperature of the actuator housing will rise ; if the on-site pipeline fluid is higher than 80℃, please contact our company in advance.Contact with the Ministry to propose a specific solution; (the connection with the valve needs to increase the bracket for heat insulation)
1.4 Pipeline high frequency vibration conditions
– Intelligent actuators under high-frequency vibration conditions require separate installation;
2.Actuator output connection
-The fange mounting hole at the bottom of the actuator is lSO5211 standard. lf the valve connection size does not conform to the standard,please contact our company’s technical department in advance to propose a specific solution;(before leaving the factory)(According to customer requirements, re-punch holes or produce brackets and connecting sleeves)
-According to the different connecting spindles of the valve, the inner hole at the bottom of the actuator can be replaced with different sizes such as square holes , round holes and bilateral holes; the replacement method is simple, just use circlip pliers to take out the spline sleeve bottom the circlip can be replaced;
3.Installation sequence of actuator and valve

Note:
This figure only shows the installation sequence and can be used as a reference. The actual actuator shall prevail.

4.Electrical wiring
-Remove the plug for external cable access, please use an explosion-proof connector or explosion-proof cable hose with an external thread of NPT3/4;
-lf the cable connector does not meet the electrical interface of the actuator, it may cause the internal sealing level to drop and fail to meet the protection requirements, or the actuator will be damaged by water entering the inside;
– When using electrical wires, take full waterproof measures;
– Remove the upper cover of the actuator,use a fat-blade screwdriver to press down the metal shrapnel in the small hole on the terminal, and at the sametime the wire is smoothly inserted into the side trminal hole,pull out the screwdriver ,the internal spring clamping mechanism of the terminal can reliably clamp the wire;

Note:
1.Before completing the wiring check, do not swich on the power supply. Shor-circuit and wrong wiring will cause permanent damage to the actuatord!
2.Please pay attention to the switch instructions, please do not use brute force on the hand wheel/handle when it exceeds the fully open an fully cosed positions, so as not to cause damage to the actuator mechanism!
Debugging instructions
1.Mechanical limit adjustment
Losen the mechanical limit screw and limit nut, turn the handwheel with the left hand and press the switch handle with the right hand in the direction of the arrow to engage the internal clutch of the mechanism to reach the manuel function state (switcing hand when the power is turned on) The handle automatically resets without human intervention), continue to rotate the handwheel clockwise to move the actuator to the fully closed position,rotate the limit screw, and stop turning when it his the internal sector worm gear.Rotate two turns to the left, and finally tighten the nut.In this way, the position of the mechanical limit when the actuator is fully closed is set. Rotate the handwheel in the fully open position counterclockwise and set it in the same way.

Note:
POQ series 006 type to 060 type manual switch requires a switch handle (automatic reset function when power is on), 08O type to 200 type does not need a switch handle
2.Electronic travel limit adjustment
Manually close the valve to the position to loosen the switch direction limit cam, adjust it to the position where the limit switch is just pressed down, and then lock the limit cam, so that the position of the electrical limit when the actuator is fully closed is adjusted;The position when fully open can be set in the same way;

3.Adjustment of overload protection device
Under the normal working pressure of the valve, adjust the overload cam so that it just touches the roller of the corresponding micro switch,but it can’t be pressed.When the required torque to openor close the valve is greater than the factory rated torque, the overload rotating shaft will rotate clockwise or counterclockwise, driving the upper overloadcam to press the micro switch to stop the function and output a set ofover torque indications.To protect the electric valve from damage.

Note:
The overload protection device has been adjusted before leaving the factory. in principle, no further adjustment is required ,f djustment is requiredthe valve needs to be adjusted under normal working pressure conditions
4.Potentiometer adjustment
The potentiometer is used as a feedback output in the actuator, and there are three output terminals, of which the terminal pin ② is connected to the sliding arm of the potentiometer. When the terminal pin of ① is connected to the actuator to open ,the resistance between it and the sliding arm keeps decreasing one end; when the pin of terminal ③ is connected to the actuator to close the action,the resistance to the sliding arm keeps decreasing one end (note: potentiometer)There should be no resistance value crossing zero, umping phenomenon).Use the handwheel to turn the valve to the fully open position, and use a multimeter to measure it, and adjust the resistance of the terminals ①② on the wiring terminals to between 40Ω and 65Ω. If it is not correct, it can be adjusted by turning the transmission gear on the potentiometer.

5.Position indicator adjustment
First close the valve to the correct position, disassemble the 3D window protective cover and 3D transparent protective cover, use an Allen key to loosen the 3D indicator column, rotate it to the correct position and lock it,and then reset and install it in turn (Picture 1). First close the valve to the correct position, disassemble the Ex upper cover, loosen the indicator plate with a Phillips screwdriver, rotate it to the positive position and lock it, and then reset and install it in sequence (Figure 2).